I = P / VNo power factor needed for DC circuits.
Accurately convert watts to amps for AC circuits where you know the power factor. Power factor (PF) accounts for the phase difference between voltage and current in reactive loads like motors and transformers.
Power factor varies by load. Use the equipment value when available.
I = P / VCustom voltage is always supported.
I = P / VNo power factor needed for DC circuits.
I = P / (V × PF)Single-phase AC — multiply voltage by power factor.
I = P / (√3 × V × PF)Three-phase AC — divide by √3 ≈ 1.732.
Power factor is the ratio of real power (watts) to apparent power (volt-amps). It ranges from 0 to 1. A PF of 1.0 means all current does useful work. Lower PF means higher current for the same watts.
Most AC induction motors have a full-load PF of 0.80 to 0.92. Check the motor nameplate for the exact value. Use 0.85 if no data is available.